The three limits
| Conductors in the conduit | Maximum fill |
|---|---|
| One | 53% |
| Two | 31% |
| More than two | 40% |
NEC Chapter 9, Table 1.
How it’s worked out
fill = conductors × conductor area ÷ conduit area
9 × 0.0133 ÷ 0.533 = 22.5%
9 × 0.0133 ÷ 0.533 = 22.5%
Conduit areas come from Chapter 9, Table 4. Conductor areas come from Table 5.
12 AWG THHN in EMT
| Trade size | Most conductors at 40% |
|---|---|
| 1/2 in | 9 |
| 3/4 in | 16 |
| 1 in | 26 |
| 1 1/4 in | 45 |
| 1 1/2 in | 61 |
| 2 in | 101 |
Two things fill doesn’t cover
- Derating. More than three current carrying conductors in one conduit means reduced ampacity.
- Nipples. A conduit 24 inches or shorter can be filled to 60%.
Check the current NEC and your local amendments before you pull wire.