Tools  /  Voltage drop

Voltage drop calculator

Voltage lost over a run of wire, and the size that keeps it under 3%.

Voltage drop
5.3%

6.3 volts lost. 113.7 volts at the load.

Over 3%. 8 AWG brings it to 2.1%.

How it’s worked outVD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.3 Vdrop = 6.3 ÷ 120 = 5.3%
  • K = 12.9 for copper
  • Table 8: 12 AWG, 6,530 circular mils

This tool is a check. The adopted code and the authority having jurisdiction decide.

The formula

single phase: VD = 2 × K × I × L ÷ CM
three phase: VD = 1.732 × K × I × L ÷ CM

K is 12.9 for copper and 21.2 for aluminum. I is the load in amps, L the one way length in feet, and CM the wire’s area in circular mils.

This run, three sizes

WireCircular milsVolts lostDrop
12 AWG6,5306.35.3%
10 AWG10,3804.03.3%
8 AWG16,5102.52.1%

What the code says

The NEC recommends no more than 3% on a branch circuit or a feeder, and 5% across both. In most cases that’s a recommendation and not a rule, though some specs and energy codes require it.

Check the current NEC and your local amendments before you size a run.

01  Questions

What people ask next.

Is voltage drop a code violation?

Usually not by itself. The 3% and 5% figures are recommendations in the NEC, but a spec or energy code can make them required.

Does a longer run always need bigger wire?

Not always, but drop grows with length. Run the numbers on anything over about 100 feet.