The formula
three phase: VD = 1.732 × K × I × L ÷ CM
K is 12.9 for copper and 21.2 for aluminum. I is the load in amps, L the one way length in feet, and CM the wire’s area in circular mils.
This run, three sizes
| Wire | Circular mils | Volts lost | Drop |
|---|---|---|---|
| 12 AWG | 6,530 | 6.3 | 5.3% |
| 10 AWG | 10,380 | 4.0 | 3.3% |
| 8 AWG | 16,510 | 2.5 | 2.1% |
What the code says
The NEC recommends no more than 3% on a branch circuit or a feeder, and 5% across both. In most cases that’s a recommendation and not a rule, though some specs and energy codes require it.
Check the current NEC and your local amendments before you size a run.